Question: 1 / 400

What must be considered when determining the ampacity of service-entrance conductors?

The sum of continuous loads only

Noncontinuous loads plus 100 percent of continuous loads

Noncontinuous loads plus 125 percent of continuous loads

When determining the ampacity of service-entrance conductors, it is essential to account for both continuous and noncontinuous loads. Continuous loads are those that operate for three hours or more at their maximum rating, while noncontinuous loads are those that operate for less than three hours.

The National Electrical Code (NEC) specifies that for service-entrance conductors, you should calculate the total demand by adding the total of noncontinuous loads to 125 percent of the continuous loads. This approach is necessary to ensure that the conductors can handle the potential maximum load without overheating, as continuous loads can impose a sustained strain on the conductors. By adding 125% of continuous loads, it allows for a safety margin, which is crucial in applications where consistent power utilization may be a concern.

This methodology is in line with best practices for electrical safety and reliability, preventing issues such as conductor overheating, which could lead to insulation failure and potentially cause fire hazards. Therefore, considering noncontinuous loads in addition to the increased allowance for continuous loads ensures that the conductors are adequately sized for safe operation under expected conditions.

Get further explanation with Examzify DeepDiveBeta

Continuous loads only

Next Question

Report this question

Subscribe

Get the latest from Examzify

You can unsubscribe at any time. Read our privacy policy